NA2XH CableAL-XLPE-LSZH 0.6/1kV
Description
Designed for safety-critical environments, the NA2XH Cable complies with IEC 60502-1 and VDE 0276 Part 604, featuring XLPE insulation and a halogen-free LSZH (Low Smoke Zero Halogen) sheath. Ideal for indoor fixed wiring where fire, smoke, and toxic emissions pose risks, it ensures minimal hazard during emergencies.
Product parameters
-
Payment Type: L/C,T/T
-
Incoterm: FOB,DDP,CFR,DDU,CIF,Express Delivery,EXW,FAS,DAF,FCA,CPT,DES,CIP,DEQ
-
Min. Order: 150 Meter
Product Attributes
Packaging & Delivery
Product Description
Brand: Santai
Place Of Origin: China
Insulation Materials: Xlpe
Place Of Origin: China
Insulation Materials: Xlpe
Selling Units: Meter
Package Type: Export specific packaging
Package Type: Export specific packaging
NA2XH CableAL-XLPE-LSZH 0.6/1kV
Designed for safety-critical environments, the NA2XH Cable complies with IEC 60502-1 and VDE 0276 Part 604, featuring XLPE insulation and a halogen-free LSZH (Low Smoke Zero Halogen) sheath. Ideal for indoor fixed wiring where fire, smoke, and toxic emissions pose risks, it ensures minimal hazard during emergencies.
Rated AC 0.6/1(1.2)kV and DC 0.75/1.5(1.8)kV, it operates from -40°C to +90°C (fixed installation). The 15x (single-core) / 12x (multi-core) bending radius simplifies tight installations.
Not suitable for submerged use, this cable excels in dry or damp industrial, commercial, and public infrastructure projects. Its halogen-free composition reduces environmental impact and complies with stringent safety regulations, making it a reliable choice for hospitals, schools, and high-rise buildings.
We invest in testing solutions so you receive only the best Solar Power Special Cable/MV&LV Power Cable/Overhead Transmission Cable etc..Our world-class testing facility assures the quality and compliance of this cable through a continuous and rigorous testing regime.
APPLICATION:
XLPE insulated and halogen-free thermoplastic compound sheathed power and auxiliary fixed wiring cables for the supply of electrical energy.Installations where fire and emissions of smoke and toxic fumes create a potential threat. Not suitablefor use in water.
CHARACTERISTICS:
Voltage Rating:Uo/U (Um)AC: 0.6/1(1.2)kV DC: 0.75/1.5(1.8)kV
Temperature Rating:Fixed: -40°C to +90°C
Minimum Bending Radius:Single core: 15 x overall diameter Multi-core: 12 x overall diameter
CONSTRUCTION:
Conductor:RM: Class 2 strandedSE: Class 1 solid sector -shaped or stranded SM: Class 2 sector -shaped
Insulation:XLPE(Cross-Linked Polyethylene)
Sheath:LSZH (Low Smoke Zero Halogen)
Core ldentification:3 core: ●Green/Yellow●Blue ● Brown 4 core:●Green/Yellow●Brown ● Black ● Grey 5 core:●Green/Yellow●Blue ●Brown ● Grey 7 and more:● Black with White numbers
Sheath Colour:Black
DIMENSIONS: